cproudlock
0d9c4fdac4 Rename every copy of an MTConnect device name, not just the agent's
Set-MachineNumber rewrote one Devices.xml per variant and restarted the agent.
That is right for Okuma and eDNC, which keep the device name in that one file -
checked across 7 Okuma and 15 eDNC bay captures. Fanuc and Makino keep it in
several, and editing only the agent's copy leaves the adapter streaming under
the old identity.

It has already happened. Seven of thirty-four captured Fanuc bays have the
agent on the right machine number and the adapter still on the bay it was
imaged from: 4007 on a 7801 Toshulin, 3031 on a 7804, 2005 against 2006 on a
dual-spindle pair. Both captured Makino bays have Devices.xml on the machine
number and the other three files still on MAKINO-1.

Update-MTConnectVariantName renames across a declared set of files with the
owning services stopped first. Makino needs that ordering more than most: the
vendor's guide says the Adapter Manager rewrites the COMPLETE configuration
from memory as it stops, so an edit made while it runs is discarded, and that
the name must be identical in every file or the agent may not start.

It collects every name in play before rewriting rather than discovering one.
A bay half-renamed by the old code carries two at once, and converging on the
one that happened to be found leaves the other behind - which is the state this
is meant to end, not reproduce. Nothing is written if a service will not stop,
and whatever was stopped is started again.

Tested on Windows 11 against copies of the real captures: the 7801 bay (adapter
4007) converges to 7801 in two files and leaves the correct agent alone; the
7502 Makino bay converges all four; second runs report no changes. Service
ordering verified by process id, using stand-in services - sc.exe fakes named
after the real ones are not real services, so the service list is a parameter
defaulting to the production names.

Does not fix the bays already in this state; they need a run each.
2026-08-11 14:28:03 -04:00
cproudlock
66c24b5d59 shopfloor: stop manifest entries hijacking GE-Enforce's drive letter
GE-Enforce mounts the SFLD share on W: and holds it for the whole enforce
cycle, passing W:\<pctype> as -InstallerRoot to Install-FromManifest. Two
scripts that run inside that cycle, as SYSTEM in the same drive namespace,
mapped W: for their own use and deleted it on exit:

  Restore-UDCData.ps1     manifest PS1 entry, mounts the UDC backup share
  Update-MachineNumber.ps1  "Apply Machine Number" task, same backup share

Once W: is gone, the next manifest entry's Join-Path resolves against a dead
drive qualifier. In Windows PowerShell 5.1 that emits nothing rather than
throwing, so the null lands in Test-Path -LiteralPath and the entry dies with
"Cannot bind argument to parameter 'LiteralPath' because it is null".

Observed on a collections bay: the controller-credential entry, which runs
immediately after UDC Data Restore, failed this way while the entry one line
earlier had resolved a W: path successfully one second before.

Restore-UDCData now uses R: and Update-MachineNumber uses N: for the UDC
backup share. Neither letter is referenced anywhere else in the tree; V: was
not an option because Restore-EDncReg and Update-MachineNumber's NTLARS
restore already use it.

The re-mount at GE-Enforce.ps1:239-244 does not cover this. It runs after the
manifest loop and blames idle SMB timeout, but the whole cycle took one
second, so timeout was never the cause.
2026-08-03 17:22:50 -04:00
cproudlock
7298d433eb 9999 machine-number prompt: split into user-context Prompt + SYSTEM-context Apply
OLD design: a single 'Check Machine Number' scheduled task ran as the
logged-in user (BUILTIN\Users, Limited) on AtLogOn. It both showed the
InputBox AND tried to update HKLM\SOFTWARE\WOW6432Node\GE Aircraft
Engines\DNC\General + C:\ProgramData\UDC\udc_settings.json. To make
those non-admin writes possible, 02-MachineNumberACLs.ps1 pre-granted
BUILTIN\Users SetValue + Modify on those targets during imaging.

Three problems with that:
  1. SECURITY: any logged-in user could overwrite the machine-identity
     reg key.
  2. FRAGILE: ACL grants raced with eDNC install timing on some bays
     (eDNC reg key didn't exist yet when 02-MachineNumberACLs ran;
     OpenSubKey returned null, ACL silently skipped, Check-MachineNumber
     later failed with PermissionDenied).
  3. SILENT-SUCCESS BUG: Update-MachineNumber's Set-ItemProperty calls
     lacked -ErrorAction Stop. PermissionDenied is a non-terminating
     error in PS5.1, so the try/catch never fired. The script set
     $out.EdncUpdated=$true anyway and the dialog reported success
     while the reg value stayed at 9999. WJF capture log on FGY07FZ3
     shows this exact pattern.

NEW design - two scheduled tasks split by responsibility:

  - "Prompt Machine Number" : AtLogOn trigger, BUILTIN\Users (Limited).
    Reads current values (read-only). If 9999, shows InputBox. Writes
    typed number to C:\Logs\SFLD\machine-number-request.txt. Triggers
    SYSTEM Apply via schtasks /run. Polls for result JSON (60s timeout).
    Shows result MessageBox with TopMost so it isn't hidden behind
    other windows.

  - "Apply Machine Number" : on-demand, SYSTEM (Highest). Reads the
    request file, calls Update-MachineNumber (full HKLM + ProgramData
    access from SYSTEM context). Pulls per-machine NTLARS .reg + UDC
    settings JSON + UDC live data from the SFLD share if site-config
    has share paths. Writes result JSON. Removes request file.
    Unregisters the Prompt task on full success (Prompt itself can't
    self-unregister - Limited users can't delete a SYSTEM-owned task).

  - Default task SDDL only allows Admins + SYSTEM to read/run a
    SYSTEM-owned task. Added BUILTIN\Users GR+GX ACE via COM
    SetSecurityDescriptor so the Limited Prompt task can schtasks /run
    Apply on demand. They can read + execute it; not modify or delete.

  - Update-MachineNumber.ps1 writes now have -ErrorAction Stop so
    PermissionDenied actually fires the catch block instead of being
    swallowed.

  - 02-MachineNumberACLs.ps1 gutted to a no-op (left in place for
    Stage-Dispatcher discovery; no longer grants the ACLs). Old bays'
    existing grants are harmless since SYSTEM ignores them.

  - Register-CheckMachineNumberTask.ps1 now installs both tasks AND
    unregisters the legacy 'Check Machine Number' task name on
    re-imaging. Run-ShopfloorSetup.ps1's $skipInBaseline list now
    includes Prompt-MachineNumber.ps1 + Apply-MachineNumber.ps1 so
    they aren't auto-run during the baseline pass (only via the
    scheduled tasks).

Smoke tested end-to-end on win11 VM with ShopFloor (Limited) logging in
interactively: AtLogOn trigger fired Prompt, dialog rendered, tech
typed 7777, schtasks /run succeeded (the SDDL fix lets Limited users
trigger SYSTEM tasks), Apply ran as SYSTEM, eDNC reg + machine-number.txt
both updated to 7777, result MessageBox shown, Prompt task auto-
unregistered by Apply's cleanup step. No ACL grants needed on any user.

Apply also re-tested with -ErrorAction Stop confirming non-terminating
PermissionDenied now properly throws into the catch + populates Errors[]
+ flips $out.EdncUpdated to false - so any future write failures will
report honestly instead of silently claiming success.
2026-05-24 17:08:59 -04:00
cproudlock
3896667c90 Set-MachineNumber: handle duplicate-PC reassignment (real -> real)
Tech catches a PC imaged with a wrong machine number. Previously the
share restore (NTLARS .reg + UDC settings + UDC live data) only fired
on the placeholder->real transition, so a real->real change rewrote
only UDC JSON, eDNC reg, and MTConnect Devices.xml - leaving the wrong
NTLARS config in place.

Update-MachineNumber.ps1: replace the placeholder-only guard with an
any-change guard so the share restore block fires on reassign too.
The existing one-shot migrated/ consumption keeps live-data restore
idempotent. Also writes C:\Enrollment\machine-number.txt to keep
imaging-time scripts in sync.

Set-MachineNumber.ps1 (both collections + nocollections): show a
confirmation dialog when reassigning between two real numbers, naming
old/new and listing what gets pulled. Audit each call to
C:\Logs\Shopfloor\reassign.log.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-12 15:13:30 -04:00
cproudlock
6dcf96e40a Phase 3+4 rename reorg: repo dir renames + startnet.cmd menu
Pairs with Phase 1+2 from earlier (alias maps in Install-FromManifest,
GE-Enforce, Get-PCProfile, verify-state). See project-shopfloor-rename-reorg
memory for the plan.

Phase 3 (repo + paths):
- git mv per-PC-type dirs to gea-shopfloor-* names:
    Standard      -> gea-shopfloor-collections
    CMM           -> gea-shopfloor-cmm
    Keyence       -> gea-shopfloor-keyence
    Genspect      -> gea-shopfloor-genspect
    WaxAndTrace   -> gea-shopfloor-waxtrace
    Display       -> gea-shopfloor-display
    Lab           -> gea-shopfloor-common (folded; Timeclock+Lab merge)
- New gea-shopfloor-nocollections/ (clone of collections sans UDC scripts).
- New gea-shopfloor-heattreat/ (placeholder, README only).
- Move Standard/ntlars-backups/ -> _ntlars-backups/ (per-MN, not per-type).
- Run-ShopfloorSetup.ps1: Resolve-PCTypeDir helper walks alias group when
  the on-disk dir for the current pcType is missing. Set-MachineNumber
  helper-copy gated on collections|nocollections|legacy Standard-Machine.
- Update-MachineNumber.ps1: pcProfiles lookups try gea-shopfloor-collections
  first, fall back to legacy Standard-Machine. PowerShell 5.1 compatible
  (no null-coalesce).

Phase 4 (startnet.cmd menu):
- Choice 3 "GEA Shopfloor" now drills into a 9-item sub-menu instead of
  going straight to enrollment. Sub-cats:
    1. Machine with Collections        -> gea-shopfloor-collections
    2. Machine without Collections     -> gea-shopfloor-nocollections
    3. Common (Timeclock, Lab)         -> gea-shopfloor-common
    4. Keyence                         -> gea-shopfloor-keyence
    5. CMM                             -> gea-shopfloor-cmm
    6. Genspect                        -> gea-shopfloor-genspect
    7. Heattreat                       -> gea-shopfloor-heattreat
    8. Wax and Trace                   -> gea-shopfloor-waxtrace
    9. Display                         -> gea-shopfloor-display
- Office menu (existing 6-option) follows for every sub-cat.
- Machine number prompt only for collections + nocollections.
- pc-subtype.txt + display-type.txt no longer written. PCTYPE is a
  single full string (gea-shopfloor-*); subtype-aware code paths fall
  back to empty and resolve via the alias map.
- CMM bootstrap stage gate switched from "%PCTYPE%"=="CMM" to
  "%PCTYPE%"=="gea-shopfloor-cmm".

Test harness:
- B-enforce/run.sh PCSUBTYPE default changed from "Machine" to "" so
  single-arg invocation matches the new single-string scheme. Two-arg
  legacy form ("Standard Machine") still works via aliasing.
- B-enforce/tamper.ps1 alias-aware Test-MatrixEntryMatches mirroring
  verify-state.ps1.

Smoke-tested on win11 VM as SYSTEM via qga: B-enforce harness 5-phase
cycle (stage / baseline / tamper / heal / idempotent) passes 10/10
with PCType=gea-shopfloor-collections AND with legacy "Standard Machine"
two-arg form.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-04 08:09:16 -04:00
cproudlock
75b85bfde6 Update-MachineNumber: pull per-bay udc_settings.json from SFLD on placeholder->real
When the tech transitions a 9999-placeholder PC to its real machine number,
also restore the per-bay udc_settings_<num>.json from
\\tsgwp00525\shared\spc\udc\settings_backups\. PXE-time preinstall can't reach
this share (no SFLD creds yet), so 00-PreInstall uses the local C:\Enrollment
mirror; post-config the share is reachable, so the renumber path goes direct
to the canonical source.

Adds udcSettingsSharePath to site-config.json under Standard-Machine.

Bundles in prior uncommitted work in the same file: ntlars reg restore,
UDC data restore (CurrentData.json + ArchivedData/), MTConnect Devices.xml
inline rewrite + service restart, and one-shot consume of per-bay UDC
backup -> migrated/<timestamp>/.
2026-04-30 12:34:53 -04:00
cproudlock
85e74e5dd1 UDC settings: pre-stage from server backups, fix arg format, action prompts
Root cause found via decompiling UDC_Setup.exe: it never writes
udc_settings.json from CLI args. Instead it pulls
Settings_Backups\udc_settings_<num>.json from \\tsgwp00525\shared\SPC\UDC
-- which is unreachable at imaging time (no SFLD creds yet). Silent
File.Exists() false, settings never copy, UDC lands on Evendale defaults.

Fix: stage 80 udc_settings_*.json backups under
shopfloor-setup/Standard/udc-backups/ (same tree as ntlars-backups,
xcopy'd to C:\Enrollment\ by existing startnet.cmd). 00-PreInstall
pre-creates C:\ProgramData\UDC\udc_settings.json from the matching
backup BEFORE UDC_Setup.exe runs. Installer's server-side copy silently
fails (unreachable), our pre-staged file survives.

Also:
- preinstall.json UDC InstallArgs corrected: "West Jefferson" -9999
  (quoted spaced site + dash-prefixed number, confirmed via decompile)
- Update-MachineNumber.ps1 UDC.exe relaunch: quoted site + dash number
- Monitor-IntuneProgress: action prompts (Select Device Category after
  Phase 1; Initiate ARTS Lockdown after Phase 5/creds), Display flow
  (3-phase: Registration -> Config -> Lockdown), Phase 6 IME-based
  lockdown detection

Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
2026-04-16 08:44:34 -04:00
cproudlock
2db35c2976 UDC: correct CLI arg signature to compact site + dash-prefixed machine#
UDC_Setup.exe and UDC.exe expect:
  UDC_Setup.exe WestJefferson -7605

Not the spaced-quoted positional pair we'd been passing:
  UDC_Setup.exe "West Jefferson" 7605

The wrong format meant UDC ignored both args, fell back to defaults
(Site=Evendale, MachineNumber=blank). Combined with the kill-after-detect
window, neither value got persisted to udc_settings.json regardless of
whether UDC.exe was given time to write.

Changes:
- preinstall.json: UDC InstallArgs now "WestJefferson -9999"
- 00-PreInstall-MachineApps.ps1: site override now matches/replaces
  the compact 'WestJefferson' token (not 'West Jefferson') and uses
  siteNameCompact from site-config; targetNum extraction regex updated
  to '-(\d+)$' for the new dash-prefix format
- Update-MachineNumber.ps1: UDC.exe relaunch now passes positional
  compact-site + dash-prefixed number instead of -site/-machine flags

Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
2026-04-15 17:47:57 -04:00
cproudlock
6db170bf54 Shell defaults + eDNC reg restore from machine-number backups
- 03-ShellDefaults.ps1: Default-User TaskbarAl=0 (left), HKLM policies to
  hide Start Recommended section, kill Bing web search + suggestions,
  disable Cortana. LTSC-honoured; runs fleet-wide via baseline loop.

- ntlars-backups/: 147 per-machine eDNC registry backups renamed to
  flat <MachineNumber>.reg scheme. Historical off-by-one entries from
  the original dump rewritten to match CSV-target MachineNo.

- Standard/03-RestoreEDncConfig.ps1: at imaging time, if tech typed a
  real machine number at PXE (not 9999), import <num>.reg from the local
  staged copy. Restores eFocas IP, PPDCS serial, Hssb relays -- not just
  the bare MachineNo. Skipped on Timeclock / 9999 / missing backup.

- Update-MachineNumber.ps1: when tech later sets a real number from 9999,
  pull <num>.reg from tsgwp00525 SFLD share (ntlarsBackupSharePath in
  site-config) and reg-import it before writing the new MachineNo.

- Restore-EDncReg.ps1: shared helper (Mount-SFLDShare + Import-EDncRegBackup)
  used by both callers.

Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
2026-04-15 15:42:21 -04:00
cproudlock
7c8eb6899d Shared machine-number helper, site-config for OpenText + PreInstall, placeholder type dirs
Three optimization batches from the pipeline audit:

1. Shared Update-MachineNumber.ps1 helper (lib/)
   Extracts duplicated machine-number update logic from Configure-PC.ps1,
   Check-MachineNumber.ps1, and Set-MachineNumber.ps1 into a shared
   dot-sourceable helper at Shopfloor/lib/Update-MachineNumber.ps1.

   Exports:
     Get-CurrentMachineNumber → @{ Udc = $string; Ednc = $string }
     Update-MachineNumber -NewNumber <n> [-Site <s>] → @{ UdcUpdated; EdncUpdated; Errors }

   All three consumers now dot-source the helper instead of duplicating
   ~50 lines each. Set-MachineNumber.ps1 also migrated from inline
   Get-SiteConfig to dot-sourcing Get-PCProfile.ps1 for consistency.

2. Site-config integration for remaining scripts
   Setup-OpenText.ps1: exclude lists (profiles + shortcuts) now read from
     site-config.json opentext section, falling back to West Jefferson
     defaults. Inline Get-SiteConfig since the script runs from
     C:\PreInstall\installers\opentext\ (can't dot-source Get-PCProfile).

   00-PreInstall-MachineApps.ps1: after parsing preinstall.json, scans
     InstallArgs for "West Jefferson" and replaces with site-config
     siteName if different. Inline Get-SiteConfig for same reason.

3. Placeholder type-specific directories
   Created skeleton 01-Setup-*.ps1 scripts for all PC types so the
   directory structure is in place and Run-ShopfloorSetup's type-specific
   loop has something to iterate over:
     Genspect/01-Setup-Genspect.ps1
     Keyence/01-Setup-Keyence.ps1
     WaxAndTrace/01-Setup-WaxAndTrace.ps1
     Lab/01-Setup-Lab.ps1
   Each logs a "no type-specific apps configured yet" banner and exits.
   Fill in app installs when details are finalized; for share-based
   installs, copy the CMM/01-Setup-CMM.ps1 pattern.