Sites no longer need either MAC in site-vars. pxe_nic_mac empty: before anything changes, the playbook runs pxe-pick-nic --auto. It takes the one wired port with a link, accepts it only if pxe-nic-check calls it isolated (no LLDP/CDP/802.1X, no other DHCP server, at most 10 hosts heard in 65 s), and pins it. The choice is saved in /etc/pxe-server/nic-pick.conf and never re-guessed at boot. When it cannot tell (no link, two links, not isolated) nothing changes, and the console banner says why and to run sudo pxe-pick-nic: pull the imaging cable and plug it back in, and the port that blinked is the imaging one. Both helpers are installed before the pick, so that works after a refused first boot. The site's corp domains and allowed switches are passed to the check. corp_nic_mac empty: every other wired port (en*, eth*) is a catch-all DHCP client, so GE can be plugged in at install or later. - dnsmasq stays pinned with interface=pxe0. A new check refuses any dhcp-range outside the imaging subnet, and proxy ranges. - The catch-all ports ignore offers from 172.16.9.1. - UFW allows SSH and 9009 by source on any interface, and keeps those rules when the old any-interface rules are removed. - pxe_nic_name must not look like en*/eth* in this mode. pxe-netplan-apply.sh takes 3 or 5 args. Without a pinned GE NIC it: - renames stray names (the old pxe0 after a re-pick, a leftover corp0) to enx<mac>, so the catch-all takes them, and restores them on revert; - checks that every NIC that had a DHCP address before has one after, tracked by MAC. With both MACs set (the WJ server), netplan, the dnsmasq pin and UFW render byte-for-byte as before. Tested in the pxetest VMs: - Fresh install with no MACs and the GE link down: the imaging port was picked and pinned as pxe0 with 172.16.9.1, and dnsmasq bound DHCP to pxe0 only. GE plugged in afterwards got a lease, SSH worked, and the guard reported pxe0 isolated. - --auto refuses with two links. - The interactive pick works by pulling and replugging the link. - A 3-arg re-apply is UNCHANGED. Unit tests (fake sysfs) cover the re-pick and pinned-to-catch-all renames.
11 KiB
PXE NIC guard
The PXE server's DHCP/PXE (dnsmasq) must never serve on the GE corporate network. Each server has two NICs:
| Role | Network | Address |
|---|---|---|
| imaging | isolated imaging switch | static 172.16.9.1/24, dnsmasq |
| ge | GE corporate network | DHCP client (systemd-networkd) |
/etc/dnsmasq.d/pxe-nic-only.conf pins dnsmasq to the imaging NIC by name.
That stops dnsmasq answering on the GE NIC, but not on the imaging NIC when
that NIC itself ends up on the wrong network: a cable swap, an imaging
switch uplinked into a GE port, or a second PXE server on the same switch.
The NIC guard catches those.
What is installed
| File | Purpose |
|---|---|
/usr/local/sbin/pxe-nic-check |
the classifier |
/etc/pxe-server/nic.conf |
which NIC is which |
/etc/systemd/system/dnsmasq.service.d/nic-guard.conf |
guard before every dnsmasq start |
/etc/systemd/system/pxe-nic-check.{service,timer} |
watch every 5 min |
/usr/local/sbin/pxe-nic-carrier |
re-check on imaging cable moves |
/etc/networkd-dispatcher/<state>.d/50-pxe-nic-carrier |
calls it on link changes |
/etc/systemd/system/pxe-nic-carrier.service |
the re-check after carrier gain |
/run/pxe-nic-status.json |
last result, read by the webapp |
Sources: playbook/pxe-server-helpers/, installed by pxe_server_setup.yml
(vars pxe_nic_mac, corp_nic_mac, pxe_corp_domain_suffixes,
pxe_nic_allowed_switches; pxe_imaging_mac / pxe_ge_mac are derived
from the first two). The same MACs pin the NICs in netplan
(playbook/templates/netplan-pxe.yaml.j2, names pxe0 / corp0) and in
/etc/dnsmasq.d/pxe-nic-only.conf. With pxe_nic_mac empty the playbook
picks the imaging NIC at install time with pxe-pick-nic --auto, which
runs this check on the one port with a link (--iface X --probe, 65 s)
and accepts only "isolated". With corp_nic_mac empty ge_mac is blank
and the GE NIC is whichever other port holds a DHCP lease.
How it decides
It listens on each NIC (raw socket, sends nothing; it joins the STP, 802.1X, LLDP, CDP and PVST+ multicast groups so a NIC that is not promiscuous still hears them) for:
- LLDP and CDP: managed switches announce themselves. GE switches do; the unmanaged imaging switch does not.
- 802.1X EAPOL from an authenticator: GE ports ask for port authentication (EAP Request, Success or Failure). EAPOL that clients send is ignored: iPXE sends three EAPOL-Starts every time it opens a NIC and Windows sends Starts and EAP Responses, so a bay PXE-booting on the imaging switch is not mistaken for a GE port. Those frames show up only as "N client EAPOL frames ignored".
- DHCP OFFER/ACK from any other server.
- STP and the count of distinct ARP hosts: reported, never decisive.
On the imaging NIC it also sends one DHCPDISCOVER and collects offers for 6 s. On the GE NIC it reads the networkd lease instead (no traffic).
| Verdict | Meaning |
|---|---|
isolated |
no foreign DHCP, no LLDP/CDP/EAPOL |
ge |
LLDP, CDP or EAPOL seen, or a DHCP server whose domain ends in a corp suffix (geaerospace.net, ge.com; whole labels, so notgeaerospace.net does not count) |
foreign-dhcp |
another DHCP server, no corp domain |
no-link |
no carrier |
error |
the check itself failed |
Healthy: imaging NIC isolated (or no-link), GE NIC ge.
Our own dnsmasq never counts. An offer whose server id is our own address but comes from a MAC that is not ours is a second PXE server and DOES count.
If the imaging switch is itself a managed switch that sends LLDP/CDP, put
its LLDP system name, CDP device id or chassis MAC in allowed_switches
(pxe_nic_allowed_switches), or the guard will block dnsmasq. 802.1X is
never allowed.
Modes
pxe-nic-check- check every NIC (60 s), print a summary.--json,--write,--probe(imaging DHCP probe),--iface NAME,--window S.pxe-nic-check --guard- dnsmasqExecStartPre. Imaging NIC only, about 6 s. Exit 1 = do not serve: dnsmasq does not start. A bug or no link exits 0 (fail open) with an error line in the journal.pxe-nic-check --watch- the timer. On a bad imaging verdict it runssystemctl stop dnsmasqand logs CRIT. It never starts dnsmasq. If dnsmasq was (re)started during the 60 s window (an operator, or the carrier hook, restarted it and its guard passed), the watch re-checks for about 6 s and stops dnsmasq only if that still says blocked; if dnsmasq is already stopped it only logs.pxe-nic-carrier- the networkd-dispatcher hook. Only the imaging NIC (or its bridge ports) counts; GE NIC events are ignored. Carrier lost: dnsmasq is stopped at once if it was running. Carrier back: after 2 s,pxe-nic-carrier.servicerestarts dnsmasq if it was running or the hook stopped it, so the guard checks the new network before dnsmasq serves again; dnsmasq that an operator or the watch stopped stays stopped. A bridge with several ports stops dnsmasq when any one of them loses carrier. Log:journalctl -t pxe-nic-carrier.
Every start or restart of dnsmasq runs the guard, so systemctl restart dnsmasq and the @reboot cron restart take about 6 s longer than before.
Reading it
sudo pxe-nic-check # full summary, 60 s
cat /run/pxe-nic-status.json # last guard/watch result
journalctl -u dnsmasq -b | grep pxe-nic-check
journalctl -u pxe-nic-check -b
journalctl -t pxe-nic-carrier -b # cable unplug / replug
dnsmasq will not start
journalctl -u dnsmasq -b | grep pxe-nic-checkshows the evidence, e.g.REFUSING to start dnsmasq: imaging NIC br-pxe verdict ge: LLDP from WJ-IDF2 port Gi1/0/14.- Check the imaging cabling: the imaging NIC must go to the imaging switch only, and that switch must not be uplinked anywhere.
sudo pxe-nic-checkuntil the imaging NIC readsisolated.sudo systemctl start dnsmasq(runs the guard again).
Floor tests (run with the floor idle)
All three tests stop imaging for a few minutes. Have console or GE-side SSH access to the server; do not rely on the imaging network for the session.
(a) Rogue DHCP on the imaging switch: expect the alarm
- Confirm the baseline:
sudo pxe-nic-check --probeshows the imaging NICisolatedanddnsmasq_boundtrue. - Plug a device that runs a DHCP server into a free port of the IMAGING switch (a spare home router with DHCP on, LAN port only, nothing in its WAN port; or a laptop running dnsmasq).
- Run the watch now instead of waiting up to 5 min:
sudo systemctl start pxe-nic-check.service - Expect:
journalctl -u pxe-nic-check -n 20has a CRIT lineimaging NIC is NOT isolated, stopping dnsmasq: ... verdict foreign-dhcp: DHCP from 192.168.x.1, ...(orgeif the router sends LLDP).systemctl is-active dnsmasqisinactive./run/pxe-nic-status.jsonhas"dhcp_guard": {"state": "blocked", ...}.
- Prove the guard too:
sudo systemctl start dnsmasqmust FAIL, andjournalctl -u dnsmasq -n 20showsREFUSING to start dnsmasq. - Unplug the rogue device.
sudo pxe-nic-check --probeshowsisolated.sudo systemctl start dnsmasqstarts. PXE-boot one client to confirm.
(b) Cable swap into a GE port: expect the guard to refuse dnsmasq
dnsmasq must be stopped BEFORE the cable moves, so it never serves on GE.
sudo systemctl stop dnsmasq;systemctl is-active dnsmasqmust sayinactive. Do not reboot during the test (the@rebootcron restarts dnsmasq; the guard would still block it, but do not test that way).- Move the IMAGING NIC's cable from the imaging switch into a live GE
network port. Wait for link:
ip -br linkshows the imaging NICUP. The carrier hook sees the link come up and runs the guard once (one DHCPDISCOVER) to refresh the status file; with dnsmasq stopped it does not start it.journalctl -t pxe-nic-carrier -n 5showsdnsmasq was not running, left stopped. - Run the guard by hand first:
sudo pxe-nic-check --guard; echo "exit $?"Expectexit 1and aREFUSING to start dnsmasqline naming LLDP/CDP, 802.1X, orDHCP from 10.x.x.x, domain ....geaerospace.net. This sends one DHCPDISCOVER on the GE port, the same as any PC being plugged in. To send nothing, use--no-probe --window 60instead and rely on LLDP/CDP/802.1X (switches announce every 30-60 s). If it exits 0, STOP: do not start dnsmasq. Move the cable back and send the output ofsudo pxe-nic-check --probe --json. - Only after step 3 exited 1:
sudo systemctl start dnsmasq. ExpectJob for dnsmasq.service failed;systemctl is-active dnsmasqsaysfailed;journalctl -u dnsmasq -n 20showsREFUSING. - Move the cable back to the imaging switch.
sudo pxe-nic-check --probeshows the imaging NICisolated.sudo systemctl start dnsmasqstarts. PXE-boot one client to confirm.
(c) Imaging cable unplugged and replugged: expect stop, re-check, start
- dnsmasq running, imaging NIC
isolated. - Unplug the imaging NIC's cable. Within a second
journalctl -t pxe-nic-carrier -n 5showscarrier lost on imaging NIC ... stopped dnsmasqandsystemctl is-active dnsmasqisinactive. - Plug it back into the imaging switch. About 10 s later the journal
shows
guard passed, dnsmasq (re)startedand dnsmasq isactive. Had it gone into a GE port instead, the guard refuses: the journal showsdnsmasq NOT startedand dnsmasq stays down.
Status file
/run/pxe-nic-status.json, mode 0644, replaced atomically:
{"checked_at": "2026-10-14T16:47:09-04:00", "duration_s": 60,
"dhcp_guard": {"state": "allowed"|"blocked"|"unknown", "reason": "..."},
"interfaces": [{"iface": "br-pxe", "mac": "aa:bb:..", "role": "imaging"|"ge"|"other",
"link": "up"|"down", "speed_mbps": 5000, "addrs": ["172.16.9.1/24"],
"verdict": "isolated"|"ge"|"foreign-dhcp"|"no-link"|"error", "evidence": ["..."],
"dhcp_servers": [{"server": "10.1.2.3", "domain": "x.geaerospace.net", "own": false}],
"switch": {"lldp": [{"system": "...", "port": "...", "vlan": null}],
"cdp": [{"device": "...", "port": "..."}], "eapol": false, "stp": false},
"arp_hosts": 3, "dnsmasq_bound": true}]}
dnsmasq_bound is null when it cannot be told (no ss). A bridge
(br-pxe) is reported as one interface; its ports are listened on too,
because LLDP and 802.1X frames stop at the port and never reach the bridge.