cproudlock de3018512a 09-Setup-WaxAndTrace: fix broken-filename detection (Get-ChildItem -Filter)
The direct-copy bypass added earlier was never firing - Get-ChildItem -Filter
uses Win32 filename filtering and does NOT honor PowerShell wildcards or
character classes. The previous detection filter '*[0-9] _*.txt' matched
literal bracket-zero-through-nine text, which never appears in any
filename. $hasBrokenFilenames was therefore always False, and every
218-378-13 series cal apply fell through to the vendor setup.exe which
crashes with System.ArgumentException (exit -532462766).

Confirmed via debug-waxtrace-cal.ps1 log on WJF00159: section 6 reports
the on-disk script has the direct-copy fix, section 7 shows the actual
runtime log line 'running cal Setup.exe' followed by exit -532462766.
The "fix" was never executing because the gate was broken.

Replace -Filter with Get-ChildItem -File + Where-Object regex match on
' _\d+\.txt$' which catches the actual buggy filename pattern (space-
underscore-digits-.txt at end of name) regardless of probe series.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-22 14:09:10 -04:00

275 lines
14 KiB
PowerShell

# 09-Setup-WaxAndTrace.ps1 - Wax and Trace pc-type setup (Mitutoyo FormTracePak v6.213)
#
# Imaging-time install. Installs prereqs from manifest, then runs the
# Mitutoyo FormTracePak v6.213 vendor installer from a mounted ISO. The
# VB6 Setup.exe wrapper checks GetDriveType() == DRIVE_CDROM; Mount-DiskImage
# satisfies that (a real CD drive isn't required). Per-asset calibration ISO
# applies last.
#
# Layout at C:\WaxTrace-Install\ (xcopied by startnet.cmd):
# waxtrace-manifest.json
# 09-Setup-WaxAndTrace.ps1 (this file)
# prereqs\vcredist_x86.exe (VC++ 2008 x86)
# prereqs\vcredist_x64.exe (VC++ 2008 x64)
# prereqs\vc_redist.x86.exe (VC++ 2017 x86)
# prereqs\vc_redist.x64.exe (VC++ 2017 x64)
# prereqs\HASPUserSetup.exe (Sentinel Runtime / HASP dongle driver)
# formtracepak\FORMTRACEPAK-V6.213.iso (vendor installer ISO, ~2 GB)
# calibrations\CAL-<asset>_serial-<sn>_probe-<probe>.iso (per-machine)
#
# Per-machine calibration is applied separately (mount cal ISO + run its
# Setup.exe), keyed by C:\Enrollment\machine-number.txt.
#
# Legacy captured/ replay path (V6.0 zip + reg) retired 2026-05-21. The
# captured-binary/ payload is still in the repo as a fallback - if the
# v6.213 vendor install fails on a bay, fall back to the captured path
# manually. See git history for the prior shape.
#
# Log: C:\Logs\WaxTrace\09-Setup-WaxAndTrace.log
# C:\Logs\WaxTrace\install.log (written by Install-FromManifest)
$ErrorActionPreference = 'Continue'
# Mirror the CMM pattern (09-Setup-CMM.ps1): the script itself lives in the
# shopfloor-setup tree (xcopied during WinPE), but the bulky bootstrap bundle
# (prereqs + captured master + cal ISOs) lives at C:\WaxTrace-Install\, put
# there by startnet.cmd from Y:\installers-post\waxtrace\ at imaging time.
$stagingRoot = 'C:\WaxTrace-Install'
$manifestPath = Join-Path $stagingRoot 'waxtrace-manifest.json'
$libSource = Join-Path $PSScriptRoot '..\common\lib\Install-FromManifest.ps1'
$logDir = 'C:\Logs\WaxTrace'
$installLog = Join-Path $logDir 'install.log'
$transcriptLog = Join-Path $logDir '09-Setup-WaxAndTrace.log'
if (-not (Test-Path $logDir)) {
New-Item -Path $logDir -ItemType Directory -Force | Out-Null
}
try { Start-Transcript -Path $transcriptLog -Append -Force | Out-Null } catch {}
function Write-WTLog {
param([string]$Message, [string]$Level = 'INFO')
$stamp = Get-Date -Format "yyyy-MM-dd HH:mm:ss"
Write-Host "[$stamp] [$Level] $Message"
}
Write-WTLog "================================================================"
Write-WTLog "=== WaxTrace Setup (imaging-time) session start (PID $PID) ==="
Write-WTLog "Running as: $([System.Security.Principal.WindowsIdentity]::GetCurrent().Name)"
Write-WTLog "Script root: $PSScriptRoot"
Write-WTLog "================================================================"
# Status push - best-effort.
$pxeStatusLib = Join-Path $PSScriptRoot '..\Shopfloor\lib\Send-PxeStatus.ps1'
if (Test-Path $pxeStatusLib) {
try { . $pxeStatusLib; Send-PxeStatus -Stage '09-Setup-WaxAndTrace: starting' -StageIndex 3 -StageTotal 8 } catch { }
}
foreach ($file in @('pc-type.txt','machine-number.txt')) {
$path = "C:\Enrollment\$file"
if (Test-Path -LiteralPath $path) {
$content = (Get-Content -LiteralPath $path -First 1 -ErrorAction SilentlyContinue).Trim()
Write-WTLog " $file = $content"
} else {
Write-WTLog " $file = (not present)"
}
}
# ============================================================================
# Step 1: Prereqs via manifest (VC++ 2008 + 2017, HASP/Sentinel)
# ============================================================================
if (-not (Test-Path $manifestPath)) {
Write-WTLog "waxtrace-manifest.json not found at $manifestPath" 'ERROR'
} elseif (-not (Test-Path $libSource)) {
Write-WTLog "Install-FromManifest.ps1 not found at $libSource" 'ERROR'
} else {
Write-WTLog "Running Install-FromManifest (InstallerRoot=$PSScriptRoot)"
& $libSource -ManifestPath $manifestPath -InstallerRoot $stagingRoot -LogFile $installLog
$rc = $LASTEXITCODE
Write-WTLog "Install-FromManifest returned $rc"
}
# ============================================================================
# Step 2: FormTracePak v6.213 vendor install (Mount-DiskImage + Setup.exe)
# ============================================================================
# Detection: skip if Formtracepak already present (re-run safe).
$ftpakExe = 'C:\Program Files (x86)\MitutoyoApp\Formtracepak\Formtracepak.exe'
if (Test-Path -LiteralPath $ftpakExe) {
Write-WTLog "Formtracepak.exe already present - skipping vendor install"
} else {
$ftpakIso = Join-Path $stagingRoot 'formtracepak\FORMTRACEPAK-V6.213.iso'
if (-not (Test-Path -LiteralPath $ftpakIso)) {
Write-WTLog "FormTracePak ISO not found at $ftpakIso" 'ERROR'
} else {
Write-WTLog "Mounting FormTracePak ISO: $ftpakIso"
try {
$img = Mount-DiskImage -ImagePath $ftpakIso -PassThru -ErrorAction Stop
Start-Sleep -Seconds 8
$vol = Get-DiskImage -ImagePath $ftpakIso | Get-Volume
$ftpakDrive = $vol.DriveLetter
if (-not $ftpakDrive) {
Write-WTLog " Mount succeeded but no drive letter assigned" 'ERROR'
} else {
Write-WTLog " mounted at ${ftpakDrive}: (volume label=$($vol.FileSystemLabel))"
$setupExe = "${ftpakDrive}:\Setup.exe"
if (-not [System.IO.File]::Exists($setupExe)) {
Write-WTLog " Setup.exe not found at $setupExe" 'ERROR'
} else {
Write-WTLog " running $setupExe (VB6 wrapper - requires DRIVE_CDROM)"
# Setup.exe is the VB6 wrapper. /silent + /qn flags often
# ignored - the wrapper drives appSetup.exe + msiexec from
# its own UI. If the wrapper insists on interactive, a tech
# at the bay clicks through. Acceptable today; quieter
# path is a future improvement (drive msiexec direct on
# the wrapper's bundled MSIs).
try {
$p = Start-Process -FilePath $setupExe `
-WorkingDirectory "${ftpakDrive}:\" `
-ArgumentList '/silent' `
-Wait -PassThru
Write-WTLog " Setup.exe exit $($p.ExitCode)"
} catch {
Write-WTLog " Setup.exe failed: $_" 'ERROR'
}
}
}
Dismount-DiskImage -ImagePath $ftpakIso -ErrorAction SilentlyContinue | Out-Null
Write-WTLog " FormTracePak ISO dismounted"
} catch {
Write-WTLog " Mount-DiskImage failed: $_" 'ERROR'
}
}
}
# ============================================================================
# Step 3: Per-machine calibration ISO (mount + apply via cal Setup.exe)
# ============================================================================
# Cal ISOs are keyed by asset_tag. Read machine-number.txt to pick the right
# ISO. Each cal ISO is ~1.7MB and contains a tiny Mitutoyo wrapper Setup.exe
# plus data/*.txt compensation tables for the bay's specific probe + serial.
$mnPath = 'C:\Enrollment\machine-number.txt'
$asset = $null
if (Test-Path -LiteralPath $mnPath) {
$asset = (Get-Content -LiteralPath $mnPath -First 1 -ErrorAction SilentlyContinue).Trim()
}
if (-not $asset) {
Write-WTLog "machine-number.txt missing or empty - skipping calibration apply" 'WARN'
} else {
$calDir = Join-Path $stagingRoot 'calibrations'
$candidate = Get-ChildItem $calDir -Filter "CAL-${asset}_*.iso" -ErrorAction SilentlyContinue | Select-Object -First 1
if (-not $candidate) {
Write-WTLog "No cal ISO matched CAL-${asset}_*.iso in $calDir - skipping" 'WARN'
} else {
Write-WTLog "Mounting cal ISO: $($candidate.FullName)"
try {
$img = Mount-DiskImage -ImagePath $candidate.FullName -PassThru -ErrorAction Stop
Start-Sleep -Seconds 5
$calDrive = (Get-DiskImage -ImagePath $candidate.FullName | Get-Volume).DriveLetter
$calRoot = "${calDrive}:\"
Write-WTLog " mounted at $calRoot"
# Disc layout differs by probe series. We have observed two:
#
# Older 218-458A: E:\App.ini, E:\Setup.exe, E:\data\CVIFDLL.ini,
# E:\data\Cvif_Correction.exe, E:\data\<files>.txt.
# Vendor Setup.exe works (VB6, may prompt).
#
# Newer 218-378-13: E:\setup.bat, E:\setup.exe (.NET 4.0),
# E:\iniStatus\<png>, E:\data\cvifdll.ini,
# E:\data\<files>.txt - BUT the filenames have a
# bug: probe ID ends with a TRAILING SPACE
# ("218-378-13 _100072210.txt"). The vendor's
# .NET Setup.exe calls FileSystemInfo.set_Attributes
# on the source path and throws System.ArgumentException
# because the path contains an embedded space
# component, crashing every time
# (exit -532462766 = 0xE0434352, .NET unhandled
# exception). See diag-cal.log, WER Event 1026.
#
# We bypass the vendor wrapper entirely when the disc carries
# the buggy filenames and do a direct file copy into FormTracePak's
# data dir, renaming each file to strip the trailing space.
$srcDataDir = Join-Path $calRoot 'data'
$dstDataDir = 'C:\Program Files (x86)\MitutoyoApp\Formtracepak\data'
$hasBrokenFilenames = $false
if (Test-Path -LiteralPath $srcDataDir) {
# Get-ChildItem -Filter uses Win32 filtering and does NOT
# honor PowerShell wildcards / character classes - '[0-9]'
# would match literal bracketed text. Use -Include +
# Where-Object regex instead. The bug signature is
# ' _' (space-underscore) inside the filename, e.g.
# 'Linear_X_218-378-13 _100072210.txt'.
$hasBrokenFilenames = [bool](Get-ChildItem -LiteralPath $srcDataDir -File -ErrorAction SilentlyContinue |
Where-Object { $_.Name -match ' _\d+\.txt$' } |
Select-Object -First 1)
}
if ($hasBrokenFilenames) {
Write-WTLog " disc has trailing-space probe-ID filenames (218-378-13 series) - bypassing buggy vendor Setup.exe, doing direct copy"
if (-not (Test-Path -LiteralPath $dstDataDir)) {
Write-WTLog " destination data dir does not exist: $dstDataDir" 'ERROR'
Write-WTLog " (FormTracePak install may not be complete; cal apply aborted)" 'ERROR'
} else {
$copied = 0
Get-ChildItem -LiteralPath $srcDataDir -File -ErrorAction SilentlyContinue | ForEach-Object {
# Strip ' _' (space-underscore) -> '_' inside the filename to
# heal the Mitutoyo burn-time typo. cvifdll.ini etc unaffected.
$cleanName = $_.Name -replace ' _', '_'
$dst = Join-Path $dstDataDir $cleanName
try {
Copy-Item -LiteralPath $_.FullName -Destination $dst -Force -ErrorAction Stop
# Clear read-only on the destination so future overwrites work.
try { (Get-Item -LiteralPath $dst).Attributes = 'Normal' } catch {}
Write-WTLog " copied $($_.Name) -> $cleanName"
$copied++
} catch {
Write-WTLog " copy failed for $($_.Name): $_" 'ERROR'
}
}
Write-WTLog " direct copy complete: $copied file(s) into $dstDataDir"
}
} else {
# Older-style disc (clean filenames). Vendor Setup.exe is reliable.
$calSetup = "${calDrive}:\Setup.exe"
if (Test-Path -LiteralPath $calSetup) {
Write-WTLog " running cal Setup.exe (may prompt - VB6 wrapper, same vintage as main installer)"
$p = Start-Process -FilePath $calSetup -WorkingDirectory $calRoot -Wait -PassThru
Write-WTLog " cal Setup.exe exit $($p.ExitCode)"
} else {
Write-WTLog " cal Setup.exe not found at $calSetup" 'WARN'
}
}
Dismount-DiskImage -ImagePath $candidate.FullName -ErrorAction SilentlyContinue | Out-Null
Write-WTLog " cal ISO dismounted"
} catch {
Write-WTLog " Mount-DiskImage failed: $_" 'ERROR'
}
}
}
# ============================================================================
# Step 4: OpenText auto-start at login (HostExplorer "WJ Shopfloor" session)
# ============================================================================
$autoStartLib = Join-Path $PSScriptRoot '..\Shopfloor\lib\Set-OpenTextAutoStart.ps1'
if (Test-Path -LiteralPath $autoStartLib) {
Write-WTLog "Calling $autoStartLib"
& $autoStartLib
} else {
Write-WTLog "Set-OpenTextAutoStart.ps1 not found at $autoStartLib - OpenText auto-start NOT configured" 'WARN'
}
if (Get-Command Send-PxeStatus -ErrorAction SilentlyContinue) {
$finalStatus = if ($rc -eq 0) { 'in_progress' } else { 'failed' }
$finalErr = if ($rc -ne 0) { "Install-FromManifest exit $rc" } else { '' }
Send-PxeStatus -Stage '09-Setup-WaxAndTrace: complete' -StageIndex 4 -StageTotal 8 -Status $finalStatus -Error_ $finalErr
}
Write-WTLog "================================================================"
Write-WTLog "=== WaxTrace Setup session end ==="
Write-WTLog "================================================================"
try { Stop-Transcript | Out-Null } catch {}